The S13 is a flanged ductile iron cyclone separator for steam mains and larger duties. It is the standard installation ahead of a pressure reducing valve, a control valve or a turbine, where entrained water would otherwise erode seats and disturb control.
Flanged construction matches plant pipe classes and allows the separator to be installed as part of a prefabricated reducing station.
Design and construction
Ductile iron body with flanged inlet and outlet, an internal cyclone element to spin the flow, and a bottom drain connection. The flange faces are machined to EN 1092, and the body is rated PN16.
Key features
- High separation efficiency for steam mains
- Flanged EN 1092 PN16 connections
- Protects control valves and reducing stations from water damage
- Low pressure loss at design flow
- Bottom drain for continuous condensate removal
- Available as part of a complete reducing station
Selection and sizing
Size on steam velocity at the maximum flow and confirm the pressure class. Allow a trap at the drain, and consider a strainer upstream if the steam carries scale from new pipework.
Installation and maintenance
Mount vertically, inlet in the direction of the arrow, with a trap on the drain. Leave straight pipe upstream of the inlet so the flow enters cleanly, and insulate the body.
Options and spare parts
Cyclone inserts, gaskets and drain fittings are available.