The FT12 combines a fixed orifice with a ball float mechanism to drain very large condensate loads where the steam pressure is steady. The orifice carries the bulk of the flow continuously; the float acts as the safety element, opening fully if condensate accumulates faster than the orifice can pass it.
It is the right choice for big heat exchangers, calandrias, evaporators and steam mains where the load is high and the pressure does not swing – and where a standard float trap would be under-sized or uneconomically large.
Design and construction
Cast iron body with a bolted cover, a fixed orifice plate sized on the duty, and a float-operated valve that opens on rising condensate level. Because the orifice does the metering, capacity per unit size is far higher than a pure float trap.
Key features
- Very high capacity per line size – orifice plus float combination
- Continuous drainage with no cyclic steam loss
- Float acts as protection against condensate backup and overload
- Cast iron body for utility steam duties
- Orifice plate can be changed to re-rate the trap on site
- Simple, robust mechanism with few wearing parts
Selection and sizing
The FT12 is only appropriate where steam pressure is essentially constant: an orifice passes more steam when pressure rises and less condensate when it falls. If the plant has wide pressure swings, choose a modulating float trap or a pressure-independent control arrangement. Size the orifice on the maximum condensate load at the normal working pressure.
Installation and maintenance
Install with a strainer immediately upstream – an orifice trap is sensitive to dirt. Fit a sight glass downstream, and check the discharge at commissioning to confirm the orifice is correct. Change the orifice plate rather than the trap when the duty changes.
Options and spare parts
Orifice plates in a range of bore sizes, floats, seats and cover gaskets are available as spares.