The MST21 is a balanced pressure thermostatic steam trap. A sealed capsule filled with a fluid that follows the steam pressure-temperature curve expands and contracts to open and close the valve, so the trap holds condensate back until it has cooled slightly below steam temperature and then discharges it.
That behaviour makes it the best choice where steam loss matters more than raw capacity, and where the equipment must be drained without letting live steam through – unit heaters, dryers, cooking equipment, sterilizers and small process vessels.
Design and construction
Brass or stainless steel body depending on size, with a replaceable thermostatic capsule as the sensing and actuating element. The capsule is the only part that wears, and it can be changed in minutes without removing the body from the line.
Key features
- Discharges subcooled condensate – no live steam loss
- Replaceable capsule renews the trap without pipework work
- Fast response to load and pressure changes
- Compact, light and inexpensive to maintain
- Unaffected by orientation and by freezing in most installations
- Capsules available in a range of pressure/temperature bands
Selection and sizing
Match the capsule to the working pressure band – a capsule selected for the wrong band will either hold condensate back or pass steam. Size on the condensate load, and remember thermostatic traps discharge intermittently, so the instantaneous rate is higher than the average. For large loads or high back pressure, use a float trap instead.
Installation and maintenance
Install in any orientation, with a strainer upstream and a sight glass downstream. Do not overtighten the capsule housing. Where the trap discharges into a pressurized return main, confirm the capsule’s closing behaviour against the back pressure.
Options and spare parts
Thermostatic capsules are the standard spare and are supplied by pressure band. Body gaskets and complete trap assemblies are also available.