The IN40M is the largest of the injector range, for bulk heating duties: large storage tanks, process water systems, evaporator feed and wash plants where the heat demand is measured in hundreds of kilowatts.
Direct injection at this scale avoids the capital cost and the maintenance burden of a large heat exchanger, and it eliminates the fouling that slowly destroys exchanger performance on raw or process water.
Design and construction
Heavy stainless steel injector head with multiple nozzles, flange mounted into the vessel or main, sized to condense the full steam flow silently within the liquid.
Key features
- Very high heat input for bulk heating duties
- Direct injection with close to full latent heat recovery
- Silent operation at design conditions
- No heat transfer surface to foul or clean
- Agitation improves temperature uniformity
- Robust stainless steel construction
Selection and sizing
Size on the peak heat demand, not the average, and confirm the steam main can supply that flow without unacceptable pressure drop elsewhere. Check the vessel vent capacity and the acceptable increase in liquid volume, and confirm the injector position is always submerged.
Installation and maintenance
Mount well below the minimum liquid level and away from the outlet so heated liquid mixes before leaving. Fit a non-return valve and a trap on the steam line, and interlock the steam valve with a low level signal to protect the injector.
Options and spare parts
Nozzle heads and gaskets are available.