The LCV3 is a lift check valve: a guided disc lifts off its seat with forward flow and drops back on reverse flow, closing the line to backflow. The guided disc keeps the seat alignment accurate through many cycles, which is what a check valve needs to stay tight.
It is used on steam and condensate lines where a non-return function is required at a header, at a pump discharge, or downstream of a trap discharging into a common return main.
Design and construction
Body with a guided disc and seat, sized so that the disc lifts clear at normal flow and closes quickly when flow stops. The guided design avoids the misalignment that wears out simple swing checks on pulsating service.
Key features
- Guided disc for accurate seating over repeated cycles
- Tight closure on reverse flow
- Low pressure loss at design flow
- Suitable for steam, condensate and water
- Simple maintenance with replaceable disc and seat
- Robust body for plant utility service
Selection and sizing
Size on line size and check the velocity at normal flow: too large and the disc will chatter, too small and the pressure loss becomes significant. For pulsating flows, confirm the valve can close between pulses.
Installation and maintenance
Install with flow in the direction of the arrow, preferably with vertical up-flow for reliable gravity closure, and keep a straight run upstream. Do not install a check valve where it would trap condensate.
Options and spare parts
Discs, seats and gaskets are available.