The Gilflo ILVA is a variable area flowmeter for steam. A spring-loaded cone moves within the flow stream, and the position of the cone indicates flow rate directly on a scale; an optional transducer gives a 4-20 mA signal for the control system.
Steam is the most commonly unmeasured utility on a plant, and therefore the one most often wasted. Metering a main or a process block is the first step in any energy reduction programme, and it is what makes steam cost allocation possible.
Design and construction
Metering cone on a spring within a straight-through body, with a local indicator and an optional electronic transducer. The spring-loaded design keeps a wide measuring range and tolerates the density changes that steam flowmeters otherwise struggle with.
Key features
- Wide rangeability across the steam load range
- Low permanent pressure loss
- Local indication plus optional 4-20 mA output
- Suitable for saturated and superheated steam
- Straight-through body minimises pipework changes
- Supports energy monitoring and cost allocation
Selection and sizing
Size the meter on the normal flow, not the maximum pipe capacity, and check the turndown against the minimum flow. Confirm the steam pressure and temperature at the meter, the pipe size and whether local indication, a transmitter output or both are needed.
Installation and maintenance
Allow straight pipe runs upstream and downstream as specified for the meter, and fit a strainer upstream to protect the cone. Insulate the body to prevent condensate forming inside the meter, and mount so that the indicator is readable.
Options and spare parts
Cones, springs, transducers and gaskets are available; calibration certificates accompany new units.