The BRV2S is a direct acting pressure reducing valve in ductile iron, for steam and compressed air. A spring acts on a diaphragm that senses downstream pressure and moves the valve plug directly, so there is no pilot line to install and no external sensing pipework to maintain.
It suits smaller duties and point-of-use reduction: a single machine, a small heater battery, a tracing line or a compressed air branch where a pilot operated valve would be unnecessary.
Design and construction
Ductile iron body with a diaphragm actuator, an adjusting screw and a lapped plug and seat. Because the diaphragm acts directly on the plug, response is simple and robust, and the valve is easy to strip for cleaning.
Key features
- Self-acting – no pilot line or external sensing pipe
- Ductile iron body for steam and compressed air
- Compact and inexpensive for point-of-use reduction
- Adjustable set pressure with a locking screw
- Simple maintenance with few wearing parts
- Good shut-off at low demand
Selection and sizing
Direct acting valves have a wider proportional band than pilot operated ones, so downstream pressure droops as flow rises. Use the BRV2S where the flow is steady and the accuracy requirement is modest; for critical pressure control use the pilot operated 25P or GP-2000. Confirm inlet pressure, outlet pressure and maximum flow.
Installation and maintenance
Install with a strainer upstream and gauges either side, and allow a straight run before the valve. On steam, trap the upstream line so the valve does not see wet steam, and fit a safety valve downstream if equipment rating demands it.
Options and spare parts
Diaphragms, plugs, seats and springs are available as spares.