IN40M high capacity steam injector for large vessel and process water heating

IN40M Steam Injector

High capacity steam injector for large vessels and process water heating duties

The IN40M is the largest of the injector range, for bulk heating duties: large storage tanks, process water systems, evaporator feed and wash plants where the heat demand is measured in hundreds of kilowatts.

Direct injection at this scale avoids the capital cost and the maintenance burden of a large heat exchanger, and it eliminates the fouling that slowly destroys exchanger performance on raw or process water.

Design and construction

Heavy stainless steel injector head with multiple nozzles, flange mounted into the vessel or main, sized to condense the full steam flow silently within the liquid.

Key features

  • Very high heat input for bulk heating duties
  • Direct injection with close to full latent heat recovery
  • Silent operation at design conditions
  • No heat transfer surface to foul or clean
  • Agitation improves temperature uniformity
  • Robust stainless steel construction

Selection and sizing

Size on the peak heat demand, not the average, and confirm the steam main can supply that flow without unacceptable pressure drop elsewhere. Check the vessel vent capacity and the acceptable increase in liquid volume, and confirm the injector position is always submerged.

Installation and maintenance

Mount well below the minimum liquid level and away from the outlet so heated liquid mixes before leaving. Fit a non-return valve and a trap on the steam line, and interlock the steam valve with a low level signal to protect the injector.

Options and spare parts

Nozzle heads and gaskets are available.

Request a Quote

Technical Specifications

Standard configurations. Custom materials, connections and special testing available on request.

ParameterSpecification
Product type Steam injector (direct injection heater), high capacity
Size range DN40 - DN80 steam connection
Connections Flanged EN 1092
Body material Stainless steel
Steam pressure Up to 10 bar g (duty dependent)
Media Water and process liquids
Operation Silent condensation, no moving parts
Documentation Material certificate on request

Typical Applications

Boiler Feed & Heating

Steam injectors for direct heating, mixing and agitation in tanks and pipelines.

Energy Efficiency

Direct steam heating solutions that cut water and fuel consumption.

Related Boiler Controls

Compare more products in the same range.

Get IN40M Steam Injector Pricing Today

Send us your size, class and material requirements - quotation within 24 hours.

Request a Quote