The S1 is a ductile iron cyclone separator. Wet steam entering tangentially spins inside the body; the heavier droplets and particles are thrown to the wall and drain away at the bottom, while dry steam leaves from the top.
Dry steam is not a luxury: water droplets erode control valve seats, blind trap orifices and reduce heat transfer. A separator ahead of a control valve or a turbine is standard practice on any plant where steam quality matters.
Design and construction
Ductile iron body with a tangential inlet, a cyclone element that promotes rotation, a top steam outlet and a bottom drain connection with a trap. The internal profile is chosen so pressure loss stays low while separation efficiency remains high.
Key features
- Removes entrained water droplets and dirt from steam
- Protects control valves, traps and turbines from erosion
- Low pressure loss at design flow
- Ductile iron body for utility and process steam
- Bottom drain connection for a trap or drain valve
- Improves heat transfer by delivering dry steam
Selection and sizing
Size on steam velocity, not on line size alone: too large a separator loses efficiency, too small adds pressure loss. Confirm the flow in kg/h, the pressure and the pipe class, and allow for a trap at the drain connection. Specify a strainer upstream where the steam carries scale.
Installation and maintenance
Install with the inlet in the direction of the arrow, vertically, with the drain at the lowest point. Fit a trap on the drain so that separated condensate is removed continuously, and insulate the body to avoid condensation inside the separator.
Options and spare parts
Internal cyclone elements, gaskets and drain fittings are available.