The VB14 is a brass vacuum breaker. When pressure in a vessel or line falls below atmospheric – after a steam valve closes, when a coil cools, or when water drains away – the breaker opens and admits air, so the equipment does not collapse or suck back contaminated water.
It is the small, inexpensive device that protects tanks, calorifiers, coils and process vessels from the vacuum that forms whenever steam condenses in a closed space.
Design and construction
Brass body with a light diaphragm or disc and a seating face, arranged so that a small vacuum lifts the element and admits air, while positive pressure holds it closed. No springs, no power and no adjustment.
Key features
- Opens on vacuum to admit air and prevent collapse
- Closes tight under positive pressure – no steam or water loss
- Self-acting, with no maintenance and no power supply
- Brass body for water and steam condensate systems
- Prevents siphon backflow of contaminated water
- Compact size for direct mounting on vessels
Selection and sizing
One breaker per vessel is usually enough; for large vessels or long coils fit one at each high point. Confirm the connection size and the maximum pressure the body will see, and check the material suits the water quality – brass is not suitable for aggressive condensate.
Installation and maintenance
Mount at the top of the vessel or at the highest point of the coil, with the vent clear and protected from dirt and water. Ensure the port is not obstructed and that no isolation valve is fitted upstream where the breaker must always be available.
Options and spare parts
Diaphragms and seating elements are available as spares.