The A3S / A3SS is a stainless steel bellows sealed stop valve. Instead of a packed gland, a welded stainless steel bellows isolates the stem from the process, so there is no stem leak to atmosphere, no gland to tighten and no packing to renew at every shutdown.
That makes it the specification for steam isolation valves on inaccessible pipework, in confined plant rooms and on any line where a leaking gland would be a hazard or a continuous energy loss. The valve gives tight, repeatable shut-off for isolating a trap, a control valve or a piece of equipment.
Design and construction
Stainless steel body with a multi-ply welded bellows, a rising or non-rising stem and a lapped plug and seat. A back-up stem seal sits behind the bellows as a secondary barrier, and the bellows travel is contained so that full stroke does not fatigue the element.
Key features
- Welded stainless steel bellows – no stem leak to atmosphere
- No gland packing to renew or tighten
- Tight, repeatable shut-off on steam and process fluids
- Stainless steel body for clean and corrosive duties
- Secondary back-up stem seal behind the bellows
- Rising stem or non-rising stem options
Selection and sizing
Select on line size, pressure class and temperature: bellows have a limited stroke-to-length ratio, so confirm the valve suits the temperature cycling of the duty. State the medium, design pressure, design temperature and connection standard. For automated isolation, pair it with a pneumatic or electric actuator rather than a handwheel.
Installation and maintenance
Install with flow in the direction of the arrow and leave access above the handwheel. Do not use a bellows valve for throttling – it is an isolation valve, and throttling wears the seat and the bellows. Check the bellows periodically by looking for movement at the tell-tale port where fitted.
Options and spare parts
Bellows assemblies, plugs, seats and gaskets are available; the bellows is the part that determines the valve’s life.