The EL4611 is an electric linear actuator for modulating control valves. It replaces instrument air with a motor and gearbox, which suits plants without a compressed air system, remote installations and sites where air quality is poor.
Positioning is by a 4-20 mA signal, with the actuator holding its position when the signal is steady and driving to the set point when it changes. Manual override is provided for commissioning and for operation during a power failure.
Design and construction
Synchronous motor with a worm gearbox, anti-backlash lead screw and an electronic positioning board. Limit and torque settings protect the valve at the ends of stroke; the housing is sealed against dust and spray for outdoor and washdown areas.
Key features
- No instrument air required – independent of compressor availability
- 4-20 mA modulating control with position feedback
- Manual override for commissioning and power failure
- Adjustable stroke limits and torque protection
- Sealed housing for outdoor and humid locations
- Low running cost compared with continuous air consumption
Selection and sizing
Match the actuator thrust to the valve’s closing thrust at maximum differential pressure, and confirm the supply voltage available. Electric actuators move more slowly than pneumatic ones, so they suit temperature and pressure loops rather than fast flow loops. State the valve model, size, stroke and required fail position.
Installation and maintenance
Mount directly on the valve with the stem coupling aligned, set the stroke limits before applying full torque, and wire the positioner signal with screened cable. Provide a local isolator and follow the terminal diagram for the supply voltage supplied.
Options and spare parts
Positioner boards, motors, gearbox components and stem couplings are available as spares.