TD25 and TD25F thermodynamic steam trap for high pressure steam mains and superheat

TD25 / TD25F Thermodynamic Steam Trap

TD25 / TD25F thermodynamic steam trap for higher pressure mains, superheat and severe duty

The TD25 / TD25F thermodynamic steam trap extends the disc principle to higher pressure and more severe duty than the TD16. It is specified on high pressure steam mains, superheated steam, and plant where the trap is exposed to pressure cycling and vibration.

The F version carries an integral strainer, which protects the seating face on new or dirty pipework and on mains where scale is expected after a shutdown.

Design and construction

Heavier stainless steel body and a hardened disc lapped to the seat, designed for the higher pressure class. The disc responds to the velocity of the flashing condensate rather than to a float, so there are no mechanical linkages to wear and no water body to freeze.

Key features

  • Higher pressure rating than the TD16 for severe mains duty
  • Hardened disc and lapped seat for tight shut-off at pressure
  • Tolerant of superheat, water hammer and pressure cycling
  • Freeze-proof – no condensate body to burst
  • TD25F with integral strainer for dirty or new pipework
  • Very few wearing parts, low lifetime cost

Selection and sizing

Select TD25/TD25F where the main pressure is above the TD16 range, where superheat is present, or where the trap has a history of erosion and leakage. Confirm the differential pressure and back pressure ratio, and check that the discharge pipework and manifold are rated for the flash steam.

Installation and maintenance

Install at the low point of the main with the inlet above the disc, keep the discharge free-draining and insulate the body. On superheated steam, allow for the higher temperature at the seat and specify the correct disc grade. Fit a sight glass at commissioning to verify cycling.

Options and spare parts

Discs, strainer screens and body gaskets are available; the body is normally retained for the plant life.

Request a Quote

Technical Specifications

Standard configurations. Custom materials, connections and special testing available on request.

ParameterSpecification
Product type Thermodynamic (disc) steam trap, high pressure
Size range DN15 - DN25 (1/2" - 1")
Connections Screwed BSP or NPT; socket weld on request
Body material Stainless steel
Max operating pressure (PMA) 42 bar g
Max operating temperature (TMA) 425 °C
Variants TD25 (standard), TD25F (integral strainer)
Testing Shell and seat test to EN 12266
Documentation EN 10204 3.1 material certificate
Options Spare disc, strainer screen, high temperature disc grade

Typical Applications

Steam Mains & Drainage

Continuous condensate drainage for distribution mains, drip legs and tracing lines that protects steam quality.

Process Equipment

Automatic condensate removal for heat exchangers, jacketed pans, autoclaves and process vessels.

Clean Steam & HVAC

Condensate drainage for hygienic, pharmaceutical and building-services steam systems.

Related Steam Traps

Compare more products in the same range.

Get TD25 / TD25F Thermodynamic Steam Trap Pricing Today

Send us your size, class and material requirements - quotation within 24 hours.

Request a Quote